5-16 Terminal X30/2 Digital Input
Option: Function:
[0] * No operation
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
5-17 Terminal X30/3 Digital Input
Option: Function:
[0] * No operation
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
5-18 Terminal X30/4 Digital Input
Option: Function:
[0] * No operation
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in parameter
group 5-1* Digital Inputs except for option
[32] Pulse input.
5-19 Terminal 37 Safe Stop
Use this parameter to congure the Safe Torque O functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a eldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the VLT
®
PTC Thermistor Card MCB 112 is
mounted, congure the PTC options to get the full benet from
the alarm handling.
Option: Function:
[1] * Safe Stop Alarm Coasts the frequency converter when
Safe Torque O is activated. Manual
reset from LCP, digital input, or
eldbus.
[3] Safe Stop
Warning
Coasts the frequency converter when
Safe Torque O is activated (terminal
37 o). When the Safe Torque O
circuit is re-established, the frequency
converter continues without manual
reset.
[4] PTC 1 Alarm Coasts the frequency converter when
Safe Torque O is activated. Manual
reset from LCP, digital input, or
eldbus.
[5] PTC 1 Warning Coasts the frequency converter when
Safe Torque O is activated (terminal
37 o). When the Safe Torque O
circuit is re-established, the frequency
5-19 Terminal 37 Safe Stop
Use this parameter to congure the Safe Torque O functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a eldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the VLT
®
PTC Thermistor Card MCB 112 is
mounted, congure the PTC options to get the full benet from
the alarm handling.
Option: Function:
converter continues without manual
reset, unless a digital input set to [80]
PTC Card 1 is still enabled.
[6] PTC 1 & Relay A
This option is used when the VLT
®
PTC Thermistor Card MCB 112 gates
with a stop key through a safety relay
to terminal 37. Coasts the frequency
converter when Safe Torque O is
activated. Manual reset from LCP,
digital input, or eldbus.
[7] PTC 1 & Relay
W
This option is used when the VLT
®
PTC Thermistor Card MCB 112 gates
with a stop key through a safety relay
to terminal 37. Coasts the frequency
converter when Safe Torque O is
activated (terminal 37 o). When the
Safe Torque O circuit is re-
established, the frequency converter
continues without manual reset,
unless a digital input set to [80] PTC
Card 1 is still enabled.
[8] PTC 1 & Relay
A/W
This option makes it possible to use a
combination of alarm and warning.
[9] PTC 1 & Relay
W/A
This option makes it possible to use a
combination of alarm and warning.