5-54 Pulse Filter Time Constant #29
Range: Function:
100
ms*
[5 -
1000 ms]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the pulse lter time constant. The
pulse
lter dampens oscillations of the
feedback signal, which is an advantage if
there is a lot of noise in the system. A high
time constant value results in better
dampening, but also increases the time
delay through the lter.
5-55 Term. 33 Low Frequency
Range: Function:
100 Hz* [0 - 110000
Hz]
Enter the low frequency corresponding
to the low motor shaft speed (that is
low reference value) in
parameter 5-57 Term. 33 Low Ref./Feedb.
Value.
5-56 Term. 33 High Frequency
Range: Function:
100 Hz* [0 - 110000
Hz]
Enter the high frequency corresponding
to the high motor shaft speed (that is
high reference value) in
parameter 5-58 Term. 33 High Ref./Feedb.
Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range: Function:
0 ReferenceFeed-
backUnit*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the low reference
value [RPM] for the motor
shaft speed. This is also
the low feedback value,
see also
parameter 5-52 Term. 29
Low Ref./Feedb. Value.
5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
100 Reference-
FeedbackUnit*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the high reference
value [RPM] for the motor
shaft speed. See also
parameter 5-53 Term. 29
High Ref./Feedb. Value.
5-59 Pulse Filter Time Constant #33
Range: Function:
100
ms*
[5 - 1000
ms]
NOTICE
This parameter cannot be adjusted
while the motor is running.
5-59 Pulse Filter Time Constant #33
Range: Function:
Enter the pulse lter time constant. The
low-pass lter reduces the inuence and
dampens oscillations on the feedback
signal from the control.
This is an advantage if there is a lot of
noise in the system.
3.7.6 5-6* Pulse Outputs
Parameters for conguring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminal 27 or 29. Select terminal 27 output
in parameter 5-01 Terminal 27 Mode and terminal 29 output
in parameter 5-02 Terminal 29 Mode.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Illustration 3.32 Pulse Output
5-60 Terminal 27 Pulse Output Variable
Range: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0] * No operation Select the operation variable assigned
for terminal 27 readouts.
[45] Bus ctrl.
[48] Bus ctrl., timeout
[51] MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 87
3 3