Protections
79
7.1.1 INDICATION / WARNING ALARMS
Under Indication or Warning alarms:
The module operation is unaffected by the Protections Disabled feature. See sections entitled
Indications and Warnings elsewhere in this document.
7.1.2 SHUTDOWN / ELECTRICAL TRIP ALARMS
NOTE:- The EMERGENCY STOP input and shutdown alarm continues to operate even
when Protections Disabled has been activated.
Under Shutdown or Electrical Trip alarm conditions (excluding Emergency Stop):
The alarm is displayed on the screen as detailed in the section entitled Shutdown alarms
elsewhere in this document.
The set continues to run.
The load switch maintains its current position (it is not opened if already closed)
Shutdown Blocked also appears on the LCD screen to inform the operator that the
Protections Disabled feature has blocked the shutdown of the engine under the normally
critical fault.
The ‘shutdown’ alarm is logged by the controllers Event Log (if configured to log shutdown
alarms) and logs that the Shutdown was prevented.

Table of Contents

Other manuals for Deep Sea Electronics Plc DSE8810

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deep Sea Electronics Plc DSE8810 and is the answer not in the manual?

Deep Sea Electronics Plc DSE8810 Specifications

General IconGeneral
BrandDeep Sea Electronics Plc
ModelDSE8810
CategoryController
LanguageEnglish

Related product manuals