Front Panel Configuration
99
9.3 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
• The ‘running’ or editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
• Press and hold the button to enter the running editor.
9.3.1 ADJUSTABLE
PARAMETERS
(RUNNING CONFIGURATION EDITOR)
• Press the (up) or (down) buttons to cycle to the section you wish to view / change.
• To edit the parameter press the Tick button to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
• Press the (up) or (down) buttons to change the parameter to the required value.
• Press the Tick button to save the value. The parameter ceases flashing to indicate that it has been
saved.
• Press and hold Tick button to exit the “Running Configuration Editor”.
Section Parameter Detail Of Parameter Values
Language
Language other
English (United Kingdon)
Generator
Running Load Power Factor 0%
0.00pf
0kVAr
Load Parallel Power 0%
0kW
Load Priority Load Priority 1
Options Starting Alarms Disabled / Enabled
Decoupling Test Mode Disabled / Enabled
Voltage Voltage Adjust 0%
Frequency Frequency Adjust 0%
Display
Press/ Temp Units Pressure kPA / PSI / Bar
Temperature Deg F / Deg C
Volume Units Volume Litre / Gallons US / Gallons (UK)
Display LCD Backlight 0%
AC Graphics AC Min / Max Enable Enabled / Disabled
AC Meter Enable Enabled / Disabled
THD Screen Enable Enabled / Disabled
Engine Multi Meter Mode Enabled / Disabled
Tier 4 Screen Enabled / Disabled
Alarm Alarm Alert Box Enabled / Disabled
Summary Summary Area Graphic Bars / Connectors
Home Commissioning Screens Enabled / Disabled
Engine Speed Adjust Up / Down buttons
Time
Module Time hh:mm:ss
Module Date DD/ MM/ YYYY
Date Format MM/ DD/ YYYY OR DD/ MM/ YYYY MM/ DD/ YYYY OR DD/ MM/ YYYY