Protections
83
low oil pressure pre-alarm setting level after the Safety On timer has
expired.
Engine High
Temperature
The module detects that the engine coolant temperature has exceeded
the high engine temperature pre-alarm setting level after the Safety On
timer has expired.
Engine Low Temperature
The module detects that the engine coolant temperature has fallen
below the high engine temperature pre-alarm setting level.
Overspeed
The engine speed has risen above the overspeed pre alarm setting
Underspeed
The engine speed has fallen below the underspeed pre alarm setting
Generator Over
Frequency
The generator output frequency has risen above the pre-set pre-alarm
setting.
Generator Under
Frequency
The generator output frequency has fallen below the pre-set pre-alarm
setting after the Safety On timer has expired.
Generator Over Voltage
The generator output voltage has risen above the pre-set pre-alarm
setting.
Generator Under Voltage
The generator output voltage has fallen below the pre-set pre-alarm
setting after the Safety On timer has expired.
Insufficient Capacity
f the generator reach full load when they are in parallel with the mains
(utility). The LCD will indicate ‘INSUFFICIENT CAPACITY’ and the
COMMON ALARM LED will illuminate.
Mains Failed To Close
If the mains breaker fails to close, a warning is initiated. The LCD will
indicate ‘MAINS FAILED TO CLOSE’ and the COMMON ALARM LED
will illuminate.
Mains Failed To Open
If the mains breaker fails to open, a warning is initiated. The LCD will
indicate ‘MAINS FAILED TO OPEN’ and the COMMON ALARM LED
will illuminate.
Ecu Warning
The engine ECU has detected a warning alarm and has informed the
DSE module of this situation. The exact error is also indicated on the
module’s display.
If the module is configured for, CAN and receives an “error” message from the engine control unit,
‘CAN ECU Warning” is shown on the module’s display and a warning alarm is generated.
7.4 HIGH CURRENT WARNING ALARM
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the
pre-set trip a warning alarm initiates. The module shows Alarm Warning High Current. If this high
current condition continues for an excess period, then the alarm escalates to a shutdown condition.
For further details of the high current alarm, please see High Current Shutdown Alarm.
By default, High Current Warning Alarm is self-resetting when the overcurrent condition is removed.
However enabling ‘all warnings are latched’ will cause the alarm to latch until reset manually. This is
enabled using the DSE Configuration Suite in conjunction with a compatible PC.

Table of Contents

Other manuals for Deep Sea Electronics Plc DSE8810

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deep Sea Electronics Plc DSE8810 and is the answer not in the manual?

Deep Sea Electronics Plc DSE8810 Specifications

General IconGeneral
BrandDeep Sea Electronics Plc
ModelDSE8810
CategoryController
LanguageEnglish

Related product manuals