ASDA-B2 Chapter 7 Servo Parameters
Revision September 2013 7-67
Settings:
This parameter is used to set magnitude of the resonance suppression that is set by
parameter P2-45. If P2-46 is set to 0, the parameters P2-45 and P2-46 are both
disabled.
P2-47
ANCF
Auto Resonance Suppression Mode Selection
Address: 025EH
025FH
Operation
Interface:
Keypad/Software Communication
Related Section: N/A
Default: 1
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 2
Data Size: 16-bit
Display
Format:
Decimal
Settings:
0: Disable Auto Resonance Suppression Mode.
The setting value of P2-23~P2-24 and P2-43~P2-46 will be fixed and will not be
changed.
1: Auto Resonance Suppression Mode 1 [Non-continuous adjustment]
After the resonance is suppressed, the setting value of P2-23, P2-24, P2-43, P2-44,
P2-45 and P2-46 will be fixed and will not be changed.
2: Auto Resonance Suppression Mode 2 [Continuous adjustment]
The servo drive will perform the resonance suppression continuously (will not stop).
The setting value of P2-23, P2-24, P2-43, P2-44, P2-45 and P2-46 will not be
fixed.
When P2-47 is set to 1, the resonance suppression will be enabled automatically.
After the mechanical system becomes stable, the setting value of P2-47 will return to
0. When the mechanical system is stable, the resonance suppression point will be
memorized. When the mechanical system is not stable, if the servo drive is restarted
or P2-47 is set to 1, the servo drive will estimate the resonance suppression point
again.
When P2-47 is set to 2, the servo drive will perform the resonance suppression
continuously. When the mechanical system becomes stable, the resonance
suppression point will be memorized. When the mechanical system is not stable, if the
servo drive is restarted, the servo drive will estimate the resonance suppression point
again.
When switching the mode#1 or #2 to #0, the setting values of P2-43, P2-44, P2-45
and P2-46 will be saved automatically.
VARITEL INGENIERIA ELECTRONICA S.A.
info@varitel.com - www.varitel.com - Tel. (54) 11-4243-1171 / Fax: (54) 11-4292-7545
Manuel BaliƱa 456, Lomas de Zamora (B1832CCJ) Buenos Aires, Argentina.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics ASDA-B2 series and is the answer not in the manual?

Delta Electronics ASDA-B2 series Specifications

General IconGeneral
BrandDelta Electronics
ModelASDA-B2 series
CategoryServo Drives
LanguageEnglish

Related product manuals