12 | Messages/error elimination
D-ISC 100 x xx2
141
Code Message Measures
[083] DURAG bus: [DURAG-Bus: load current too high] 1. Determine and remove the cause (e.g. defective
sensors).
2. Reduce the load current (e.g. reduce the number
of connected sensors).
3. Replace the power supply unit.
4. Replace the main board.
[084] [Device description (Sensor) not found on SD card] Copy the required device description to the SD
card. Manually update the device description or re-
move and reinstall the sensor.
[085] [Device description (Module) not found on SD card] Copy the required device description to the SD
card and perform a restart in order to integrate the
expansion module into the system.
[086] [More then one Modbus RTU module detected] Remove excess modules from the system.
[087] [Device language in system inoperative] 1. Copy the device language to the SD card or use
current SD card.
2. Insert SD card.
3. Run 'Update device description'.
[088] [System language in system inoperative] 1. Copy the device language to the SD card or use
current SD card.
2. Insert SD card.
3. Set desired language.
[089] Die installierte Gerätebschreibungs-Datei ist zu
neu. [The installed device description file is too
new. Please update the firmware]
1. Carry out a firmware update
[090] Die installierte Sprachdatei ist zu neu. [The in-
stalled device description file is too new. Please up-
date the firmware]
1. Carry out a firmware update
[091] [Unknown display module connected] 1. Carry out a firmware update on the D-ISC 100
2. Connect a supported display module.
Table12.2: Warnings
12.4 Simple error
Note:
The English language version of the software display is indicated
in square brackets in each case.
Code Message Measures
[128] [No system settings found] 1. Copy a valid backup of the system settings to the
SD card and manually restore the backup.
2. Check system settings and correct if necessary.
Add sensors if necessary. Create a backup of the
system settings.
[129] [System setting could not be saved] 1. Repeat changes. Save system settings if neces-
sary.
2. Save system settings. Restart the system and
run "Delete flash disc". The saved system settings
are automatically restored. Check system settings
and correct if necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DURAG D-ISC 100 2 Series and is the answer not in the manual?

DURAG D-ISC 100 2 Series Specifications

General IconGeneral
BrandDURAG
ModelD-ISC 100 2 Series
CategoryControl Unit
LanguageEnglish

Related product manuals