Annex A—Protocol Implementation Conformance Statement (Normative)
(This annex is part of this Standard and is required for its use.)
BACnet Protocol Implementation Conformance Statement
Date: 5/12/14
Vendor Name: Badger Meter, Inc.
Product Name: TFX Ultra Flow meter
Product Model Number: TFX
Application Software Version: 1.20
Firmware Revision: N/A
BACnet Protocol Revision: 2
Product Description:
Clamp-on ultrasonic flow and energy meter for liquids.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
• Data Sharing-ReadProperty-B (DS-RP-B)
• Data Sharing-WriteProperty-B (DS-WP-B)
• Data Sharing - ReadProperty Multiple - B (DS-RPM-B)
• Data Sharing - WriteProperty Multiple - B (DS-WPM-B)
• Device Management-Dynamic Device Binding-B (DM-DDB-B)
• Device Management-DeviceCommunicationControl-B (DM-DCC-B)
Segmentation Capability:
Able to transmit segmented messages Window Size
Able to receive segmented messages Window Size
Standard Object Types Supported:
Dynamically
Create?
Dynamically
Delete?
Optional
Properties
Supported
Writeable
non-Required
Properties
Proprietary
Properties
Property Range
Limits
1-Device Object No No Location Location None special
25-Analog Input No No None None Double_Value None special
1-Binary Output No No None None None None special
Communications Protocols
Page 81 May 2016 TTM-UM-00136-EN-06