Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
80
Copyright © 2022 Eaton Corporation plc. All rights reserved.
8.2.2. UPS input
See the table below for details: Indicators of UPS input, output, environment and battery.
Rated input voltage 220/380 V; 230/400 V; 240/415 V
Voltage range (rectier input)
190/330–276/478VAC (-15%, +20%), 100% load
116/201–276/478VAC (-50%, +20%), 50% load
Voltage range (bypass input)
195/338–264/458VAC (default rated voltage range
±15%, max. selection range ±20%)
Rated input frequency 50 or 60 Hz, congurable
Frequency range 42-70Hz
Input phases (rectier input) 3 phases + N
Input phases (bypass input) 3 phases + N
Input power factor
> 0.99
Rated input current
See Table 3-3: Rated current at rated power and voltage
Max. input current
Distortion at rated input current, THDi < 3 %
8.2.3. UPS output
Output phases 3 phases + N
Rated output voltage 220/380 V; 230/400 V; 240/415 V, congurable
Harmonic voltage distortion (THD)
100 % linear load <2 %
100 % non-linear load <5 %
Rated output frequency 50 or 60 Hz, congurable
Rated output frequency accuracy ± 0,1 Hz
Overload capacity
102–110% load 60min;
111–125% load 10min;
126–150% load 1min;
>151% load 150ms.
Output current
See Table 3-3 : Rated current at rated power and voltage
Rated load power factor
1.0
Load power factor (allowed)
Lag 0.7 to lead 0.7