Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
82
Copyright © 2022 Eaton Corporation plc. All rights reserved.
• Please do not place the equipment in environment with extreme humidity and temperature
changes, dust, dirt, rubbles, paint, conductive particles or corrosive gases.
• Do not remove the equipment packaging before installation.
• The contractor receiving the equipment shall be responsible for equipment protection during
the storage period.
• The equipment must be stored on a solid level oor.
• Before the arrival of the equipment, an ambient temperature/humidity control plan shall be
formulated.
This product is suitable to be installed and used in the G1 environment provided in ANSI/ISA-
71.04-2013. Please see
Table 8-1
for the gas concentration limits of relevant gases.
Table 8-1: Gas concentrations recommended in Table B1 of ANSI/ISA-71.04-2013 for G1
equipment environment
Pollutants
Gases
Gas concentration/ppbv
Group A
H
2
S <3
SO
2
SO
3
<10
Cl
2
<1
NO
x
<50
Group B
HF <1
NH
3
<500
O
3
<2
Table 8-2: Requirements on the environment for transportation and storage within 1 year
Environment for transportation and storage within 1 year
(Subject to the production date on the label of equipment serial No.)
Storage site Indoor
Dust
Good
Storage temperature
< 40℃
Storage humidity
< 70% RH
Others
Stored with initial packaging
If the actual storage conditions of the machine do not meet the above storage environment, re-
evaluate the storage time according to the actual storage environment.