Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
12
Copyright © 2022 Eaton Corporation plc. All rights reserved.
Energy Saver System Mode
In ESS mode, the UPS supplies safe bus current to the load. ESS mode requires AC power that
is within an acceptable voltage and frequency range. On the display, the state of the UPS is
shown as “ESS Mode”, and the UPS is in “In Service” state. In ESS mode, the surge suppression
and ltering ensures pure electric energy for the load equipment. When any disturbance of input
power supply is detected, the UPS will switch to Online mode and continue to supply power to the
load via the inverter. If the input AC power fails or exceeds the system specications, the UPS will
switch to battery mode automatically to supply uninterrupted power to the load.
In ESS mode, the UPS constantly monitors the quality of power supply using a detection and
control algorithm, so as to meet the needs of quick mode switching. The UPS is usually capable
of switching to Online mode accurately in less than 2ms.
When the input power supply is within an acceptable range, the UPS works in a high-efciency
energy saving mode - protecting the equipment and supplying pure power to the equipment.
Within 20–100% of the rated load, the system efciency is as high as 99% in ESS mode.
Internal relay contacts
Figure 2-6: Route of the electric energy running through the UPS in ESS mode