Eaton 93PR Series - Table 3-5: Requirements on 30-40 K Connecting Terminals and Torques

Eaton 93PR Series
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
26
Copyright © 2022 Eaton Corporation plc. All rights reserved.
Table 3-5: Requirements on 30–40K connecting terminals and torques
Terminal functions Terminals Functions
Dimensions
of
connecting
terminals
Fastening
torque (Nm)
Bolt
specications
AC mains input to
UPS rectier
L1
A phase M5 2 (17.7) 13.3 mm²(M5)
L2
B phase M5 2 (17.7) 13.3 mm²(M5)
L3
C phase M5 2 (17.7) 13.3 mm²(M5)
N
N M5 2 (17.7) 13.3 mm²(M5)
AC mains input to
bypass
L1
A phase M5 2 (17.7) 13.3 mm²(M5)
L2
B phase M5 2 (17.7) 13.3 mm²(M5)
L3
C phase M5 2 (17.7) 13.3 mm²(M5)
N
N M5 2 (17.7) 13.3 mm²(M5)
UPS output to loads
L1
A phase M5 2 (17.7) 13.3 mm²(M5)
L2
B phase M5 2 (17.7) 13.3 mm²(M5)
L3
C phase M5 2 (17.7) 13.3 mm²(M5)
N
N M5 2 (17.7) 13.3 mm²(M5)
DC input
+
Battery (+)
M8 15 (133) 60 mm
²
(M8)
-
Battery (-)
M8 15 (133) 60 mm
²
(M8)
N
Battery (N)
M8 15 (133) 60 mm
²
(M8)
User grounding
Grounding M8 15 (133) 60 mm
²
(M8)