Parallel System Installation Checklist
Each cabinet in the UPS system must be placed in a proper location for installation. Do not place the UPS under the
air outlet of the air conditioner.
All conduits and cables must be properly routed to the UPS.
All power cables shall be in proper size and connected to the correct terminals.
The neutral line has been installed between cabinets as required.
The ground wire shall be properly installed.
The parallel wiring shall be correctly installed between the UPS units.
The parallel wiring shall be correctly installed.
Fireproof mud shall be lled into gaps between the cables and the cabinet.
There is adequate workspace around the UPS and other cabinets.
The startup and operational inspection of the parallel system or accessory case shall be performed by Eaton customer
service engineers.
The positive, negative and neutral wires of the battery shall be installed correctly and properly.
The external battery switch is turned off.
An alarm label has been attached to the external battery switch
.