Eaton 93PR 15-80 kW UPS
Installation and Operation Manual
42
Copyright © 2022 Eaton Corporation plc. All rights reserved.
: Terminal CN10 includes parallel CAN communication signal and REPO signal
CN10
5 6 7 8
5 6 7 8
User switch
User switch
5 6 7 8
5 6 7 8
User switch
User switch
: 1. Upon a slight touch of the button, the auxiliary battery power supply will be activated.
2. If the output of the UPS is hot(online mode/ESS mode), press the button for 10s, the UPS will transfer to
bypass.
When 5-6 are closed, the UPS will
perform emergency power off.
7-8 are idle
5-6 are connected with a short cable, and keep
them connected.
When 7-8 are open, the UPS will perform
emergency power off.