EasyManua.ls Logo

Eaton DS7 - Page 87

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
3.4 Electrical Installation
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 83
In order
to
connect a PKE motor-protective circuit-breaker with a PKE32-COM
communication cable, the following additional installation steps for the
DS7-SWD soft starter are required on top of the standard installation
procedure ( gures 55 and 56):
Remove the empty module on the PKE basic device.
Connect the PKE32-COM communication cable to the PKE basic device.
Install the PKE trip block for motor protection:
PKE-XTUWA-32 or PKE-XTUA-…
PKE trip block PKE-XTUCP-… for system protection must not be
used in combination with a soft starter DS7!