EasyManua.ls Logo

Eaton DS7 - Simple Change of Rotation

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Connection examples
7.1 Size 1 (4 – 12 A)
122 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
7.1.4 Simple change of rotation
Example for accessories required:
S3 = M22-WRK… selector switch with three switch positions
Q31 = DILA-22(…) contactor + DILA… auxiliary contact module
When in the R position (FWD), S3 will use contact 23/24 to apply the enable
signal to the DS7 soft starter (+A1 control signal terminal). The rotation is
reversed with S3 via the zero position (off) to position L (REV).
The contactor Q31 is activated and switches the enable signal via the
auxiliary contact 53/54 to the DS7 soft starter (control terminal +A1).
Q1 = Cable and motor
protection
Q21 = Soft starter
Q31 = Reversing contactor
M1 = Motor
Figure 84: Change of rotation
S3 = Rotation direction selection switch
with three contactor states
L = REV (anticlockwise rotating field)
0 = Off
R = FWD (clockwise rotating field)
Figure 85: Actuation of reversing contactor
M
3 ~
1L1
3L2
5L3
2T1
4T2
6T3
L1
L2
L3
PE
Q1
Q21
Q31
M1
I > I > I >
13 21 31 43
14 22 32 44
24 V AC/DC, 120/230 V AC
(+) U
s
() U
s
TOR
- A2 + A1 13
+ U
s
Q31
LOR
Q1
13 23
53
54
14 24
S3
(–) U
s
(+) U
s