EasyManua.ls Logo

Eaton DS7 - 4.5 Commissioning instructions

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Operation
4.5 Commissioning instructions
104 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
4.5 Commissioning instructions
.
No. Occupation
1 Set the potentiometer or the U-Start parameter as per the recommendation in the table above or,
as a general setting, turn t-Start to approximately 50% (15 s) and t-Stop to its minimum value
(0 = coasting).
2 Starting
After a maximum time of one second, the motor should start to turn, otherwise deactivate the
start signal (or on devices from 41 A the Enable signal) immediately.
If the motor has turned, proceed with point 3.
If the motor has not started, increase U-Start by around 10 % (to around 40 %).
Wait a minute for cooling and repeat step 1.
3 Optimizing t-Start: The motor should accelerate evenly from standstill to rated speed at
rated load. When it has reached rated speed, the set ramp time should have completed
(U
2
=U
LN
, = TOR).
4 Repeat the start process. After every start, wait around five minutes in order to allow the unit
to cool down.
5 Run-up optimization
If the drive accelerates faster than the set ramp time (t-Start), shorten this as much as
this application allows.
If the application requires more time for the acceleration than the set ramp time, increase
the value of t-Start – unless the load cycle of the soft starter is exceeded.
If the acceleration time is longer than the limits set in step 4 or 5, let the soft starter cool
down for 5 minutes, increase the ramp time and proceed with step 4.
6 If a stop ramp is needed, the time set (t-Stop) should be longer than the machine’s coasting time
in order for the stop ramp to have an effect. As a soft stop produces a current increase, observe
the thermal output capacity (load cycle) of the soft starter (number of starts per hour). Within this
context, the stop ramp must be considered equivalent to a start in terms of thermal
characteristics.
If the required settings for an application exceed the permissible
load cycle of the soft starter, a larger device must be selected
accordingly.
The soft starter heats up at the start. In order to avoid
overheating, make sure to adhere to the required cool-down
times without fail. If there will be frequent starts during normal
operation, the soft starter may have to be oversized under
certain circumstances and/or optional fan DS7-FAN… may have
to be used.
For more information, refer to the “Technical data” appendix.
Additional information including application and sizing examples
is found in manual MN03902001Z-EN, “Sizing Soft Starters.”

Table of Contents

Related product manuals