2.4 Power connection
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 35
2.4 Power connection
The power section should be protected according to the connection form
used.
Cable and device protection on the supply side:
Input AC… via standard fuses for cable protection or via motor-protective
circuit-breaker.
Fuses in UL compliant systems must be UL-approved.
The rated operating voltages of the fuses must be suitable for the local
mains voltage.
No fuses are required on the motor side.
The following figure shows the basic connection of motor and power
section.
Figure 18: Connecting the power section and motor
F3 = optional semiconductor fuse
Q1 = Cable protection + motor protection
Q21 = Soft starter
M1 = Motor
At the output of the soft starter (terminals 2T1, 4T2, 6T3) you must not
Connect any capacitive load (e.g. phase compensation capacitors),
Connect several soft starters in parallel,
Feed a mains voltage or a voltage from a variable frequency drive or other
voltage source.
M
3 ~
1L1
2L3
3
L5
1T2
2T4
3T6
L1
L2
L3
PE
Q1
Q21
F3
M1
I > I > I >
≦ 32 A
1L1
2L3
3L5
EP
EP
1T2
2T
4
3T6
Q21
≧ 41 A