7 Connection examples
7.3 Size 3 and 4 (41 – 200 A)
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 141
7.3.8 Starting several motors sequentially with a soft starter
If you will be starting several motors one after the other with a single soft starter,
make sure to follow the changeover sequence below:
1. Start using soft starter
2. Switch on bypass contactor Qn2 via TOR
3. Disable soft starter
4. Switch soft starter output with Qn1 to the next motor
5. Restart
When starting several motors with one soft starter the thermal
load of the soft starter (starting frequency, current load) must be
taken into account.
If the starts occur closely in succession, the soft starter must be
dimensioned larger (i.e. the soft starter must be designed with
an accordingly higher load cycle).
Due to the thermal design of the DS7 soft starters, we
recommend the use of an (optional) fan when using a DS7
series device for starting several motors.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton DS7 and is the answer not in the manual?

Eaton DS7 Specifications

General IconGeneral
Product type-
CertificationIEC/EN 60947-4-2, UL 508, CSA22.2-14
Product colorGray
Protection classI
International Protection (IP) codeIP20
Input voltage200 - 480 V
DC input voltage24 V
AC input frequency (fridge)50/60 Hz
Sustainability complianceYes
Sustainability certificatesCE
Operating temperature (T-T)-40 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Weight1800 g

Related product manuals