8 SmartWire-DT
8.10 SmartWire-DT diagnostics
214 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
8.10.4 SmartWire-DT diagnostic LEDs
The following table shows the information that can be determined based on
the SmartWire-DT diagnostic LEDs.
Table 44: SmartWire-DT diagnostic LED indications
Switching command present
For the orange SmartWire-DT diagnostic LED, the “switching command
present” message means the following:
• Profiles 1, 2, 3: DS7 Start/Stop = 1.
• Profiles 4, 5, 6, 10:EN_Set and EN_Op = 1.
• Profiles 7, 8, 9, 11:OnOff =1, Off2 =1, Off3 = 1, EN_Op = 1,
EN_Ramp = 1, Freeze = 1, EN_Set = 1, Ctl_PLC = 1.
Diagnostics
If the “Diagnostics” message appears, input byte 0, bit 4 (DIAG) will be set
to 1 as well. The message has the following meaning:
• Profiles 1 to 9: There is an advanced diagnostic alarm for soft starter DS7
or motor-protective circuit-breaker PKE.
• Profiles 10 and 11: There is an advanced diagnostic message for the
DS7-SWD soft starter
Color LED Switch
command
Position
1-0-A switch
Status Status signal
– – – off No power supply
Orange Available A Continuous light Device is operating error-free.
flashing (3 Hz) Diagnostics
Green not available 1 or
0 or
A
Continuous light Device is operating error-free.
flashing (1 Hz) • addressing process in progress
• After powering on the gateway
• After pressing the configuration button on the gateway
• Module not present in current configuration
• invalid type
flashing (3 Hz) Diagnostics