EasyManua.ls Logo

Eaton DS7 - 1.14 Function

Eaton DS7
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Device series DS7
1.14 Function
26 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
1.14 Function
DS7 soft starters use phase control for controlling the voltage of the supply
network smoothly from an adjustable start value up to 100 % of the rated
value U
LN
. This voltage control enables the inrush current of a three-phase
asynchronous motor to be limited and its starting torque to be considerably
reduced. This enables a smooth and jerk-free increase in torque, adjusted to
the load behavior of the machine.
Figure 10: Function chart
a Mains supply voltage U
LN
3 × 200 V bis 3 × 480 V
b Antiparallel thyristors in two phases with bypass contact for controlling the motor voltage
c Output voltage U
2
: three-phase, from an adjustable start voltage to 100% mains voltage with the use of a
ramp function at a constant line frequency
Output current I
2N
: 4 - 200 A at a maximum ambient air temperature of +40 °C
Rated motor shaft output P
2
: 1.5 - 110 kW with 400 or 3 - 150 HP with 480 V
d Controller card for controlling the power section
This is used to initiate control commands and set the parameters.
e SmartWire-DT interface (optional) for configuring parameters and for control and monitoring
The following limitations apply to single-phase AC motors:
U
LN
: 1 x 200 - 240 V
Output current I
2N
: 4 - 32 A
Rated motor shaft output P
2
with 230 V: 0.37 - 4 kW or 1/3 - 5 HP
M
3 ∼

Table of Contents