EasyManua.ls Logo

Eaton DS7 - Accessories; Protection, Short-Circuit Rating

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Appendix
9.5 accessories
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 221
9.5 accessories
9.5.1 Protection, short-circuit rating
Table 47: Fuses, semiconductor fuses
The following two tables, 48 and 49, provide additional information on the
high-speed semiconductor fuses.
Part no. Type “1” coordination Type 1 and 2 coordination Type 2 coordination
Cable and motor
protection
(I
q
50 kA)
1)
Cable and motor
protection
(I
q
100 kA)
Fusing with PKE
3)
Superfast
semiconductor
fuses
in addition to the
fuses for type 1
coordination
(I
q
100 kA)
Fuse holder
for semi-
conductor fuse
Part no. Part no. Part no. Quantity x Part no. Quantity x Part no.
DS7-34xSX004N0-… PKZM0-4 PKZM0-4 (+ CL-PKZ0) PKE12…-4 3 x 170M1359 3 x 170H1007
DS7-34xSX007N0-…
PKZM0-10 PKZM0-10 (+ CL-PKZ0) PKE12…-12 3 x 170M1361 3 x 170H1007
DS7-34xSX009N0-…
PKZM0-10 PKZM0-10 (+ CL-PKZ0) PKE12…-12 3 x 170M1362 3 x 170H1007
DS7-34xSX012N0-…
PKZM0-12 PKZM0-12 (+ CL-PKZ0)
2)
PKE12…-12 3 x 170M1362 3 x 170H1007
DS7-34xSX016N0-…
PKZM0-16 PKZM0-16 (+ CL-PKZ0)
2)
PKE32…-32 3 x 170M1364 3 x 170H1007
DS7-34xSX024N0-…
PKZM0-25 PKZM0-25 + (CL-PKZ0)
2)
PKE32…-32 3 x 170M1365 3 x 170H1007
DS7-34xSX032N0-…
PKZM0-32 PKZM0-32 + (CL-PKZ0)
2)
PKE32…-32 3 x 170M1366 3 x 170H1007
DS7-34xSX041N0-…
NZMN1-M50 / PKZM4-50 NZMN1-M50 / PKZM4-50 3 x 170M3013 3 x 170H3004
DS7-34xSX055N0-…
NZMN1-M63 / PKZM4-58 NZMN1-M63 / PKZM4-58 3 x 170M3013 3 x 170H3004
DS7-34xSX070N0-…
NZMN1-M80 NZMH1-M80 3 x 170M4008 3 x 170H3004
DS7-34xSX081N0-…
NZMN1-M100 NZMH1-M100 3 x 170M4008 3 x 170H3004
DS7-34xSX100N0-…
NZMN1-M100 NZMH1-M100 3 x 170M4008 3 x 170H3004
DS7-34xSX135N0-…
NZMN2-M160 NZMH2-M160 3 x 170M4010 3 x 170H3004
DS7-34xSX160N0-…
NZMN2-M200 NZMH2-M200 3 x 170M5008 3 x 170H3004
DS7-34xSX200N0-…
4)
NZMN2-M200 NZMH2-M200 3 x 170M5008 3 x 170H3004
1) Rated conditional short-circuit current Iq with PKZM…; rated short-circuit breaking capacity Icu with NZM… (according to IEC/EN 60947) for 230 V/400 V and with type
1 and 2 coordination. Auto-protected range – back-up fuse is not required.
2) + CL-PKZ0 = required current limiter
3) Wiring set PKZM0-XDM required
4) For DS7-34xSX200N0-…, only the following applies: I
q
80 kA

Table of Contents