EasyManua.ls Logo

Eaton DS7 - Delta Connection

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Engineering
2.11 Motor connection
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 43
For clockwise rotation, connect the motor and the DS7 soft starter to each
other as follows:
Table 9: Connection of Soft starters and motor
The motor’s direction of rotation can be reversed with the DS7 soft starter
if the soft starter is used together with a reversing contactor combination.
When reversing the operating direction, the output of the soft starter must
be disabled before the reverse switching is carried out. The rotating field
direction at the input will always match the rotating field direction at the
soft starter’s output ( chapter 7, “Connection examples”).
2.11.3 Delta connection
Supply system
(Mains)
Soft starter input
(Input)
Soft starter output
(Output)
Motor
(Motor)
L1 1L1 2T1 U1
L2
3L2 4T2 V1
L3
5L3 6T3 W1
PE (polyethylene)
in size 3 and size 4
only: PE,
in size 3 and size 4
only: PE,
PE,
Using inside-the-delta wiring, also referred to as a six-wire
connection (soft starter thyristors in series with the individual
motor windings and with six connection cables), is not
permissible when using a two-phase controlled DS7 soft starter!