3 Installation
3.4 Electrical Installation
86 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
3.4.5 Control section power supply
The control section in the DS7 soft starter can be powered with the following
voltages using terminals +U
s
/-U
s
(sizes 2, 3, and 4) or +U
s
/-A2 (size 1):
24 V DC/AC at DS7-340
120 - 230 V AC at DS7-342
24 V DC at DS7-34D
DS7-34D…-D soft starters can be powered directly through the
SmartWire-DT ribbon cable.
3.4.6 Internal device voltages
The DS7 soft starters do not provide any internal voltage.
3.4.7 Ground control voltage
All control signal terminals of the DS7 soft starter are galvanically isolated
from the power section. Connecting the control voltage on the DS7 soft
starter to earth is not necessary.
At a high load on the PSU supplying the SWD (many modules,
signaling lamps,
soft starters)
soft starter
DS7 can also be
supplied with control voltage through control signal terminals U
s
or
further SmartWire-DT PSUs (gateway EU5C-SWD-PF…).
If power is fed through control signal terminals
U
s
the 24 V
connection on the SWD gateway must be switched off.
Ensure that the regulator supply voltage and the control signals
always have the same potential and are supplied from the same
voltage source.
NOTICE
In size 1 devices, connection terminals +U
s
, +A1, and 13
(via the TOR contact) have a common reference potential (-A2).
The switched voltage (TOR) and the control voltages (+U
s
, +A1)
must be the same here!
If control voltage earthing requirements must be complied with
(e.g., Safety of machinery - Electrical equipment of machines,
EN 60204) earthing must be implemented at the power supply
source (control transformer, power supply unit).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton DS7 and is the answer not in the manual?

Eaton DS7 Specifications

General IconGeneral
Product type-
CertificationIEC/EN 60947-4-2, UL 508, CSA22.2-14
Product colorGray
Protection classI
International Protection (IP) codeIP20
Input voltage200 - 480 V
DC input voltage24 V
AC input frequency (fridge)50/60 Hz
Sustainability complianceYes
Sustainability certificatesCE
Operating temperature (T-T)-40 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Weight1800 g