8 SmartWire-DT
8.4 Abbreviations
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 147
The 1-0-A switch’s positions are as follows:
1: DS7-SWD soft starter is switched on
0: DS7-SWD soft starter switched off
A: switching command via SmartWire-DT
8.4 Abbreviations
The following abbreviations are used throughout this chapter:
8.5 SmartWire-DT response time
The DS7-SWD soft starter’s response time on a SmartWire-DT system is
about 150 ms. When there are two stations, the response time will increase
by about 50 ms; when there are 50, by about 400 ms.
The overload relay function (ZMR) will only be active in the 1-0-A
switch’s A position. The overload relay function will be disabled
in positions 1 and 0.
Abbreviation Meaning
ACKR Acknowledge required
TH Drive Object
EU5C-SWD-CAN SmartWire-DT gateway for connecting to a CANopen master
EU5C-SWD-DP
SmartWire-DT gateway for connecting to a PROFIBUS master
GSD Device master data
ID Identifier
PDU Protocol Data Unit
PLC Programmable Logic Controller
PNU Parameter Number
PROFIBUS Process Field Bus
RFG Ramp function generator
PLC(S) programmable logic controller