EasyManua.ls Logo

Eaton DS7 - Terminal Capacity, Control Cables, Actuating Circuit

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Appendix
9.3 Specific technical data
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 217
9.3.2 Terminal capacity, control cables, actuating circuit
The following technical data depends on size.
Size Unit Frame size 1:
4 - 12 A
Frame size 2:
16 - 32 A
Frame size 3:
41 - 100 A
Frame size 4:
135 - 200 A
General
Dimensions (W x H x D) mm 45 x 130 x 95 45 x 150 x 118 93 x 175 x 139 108 x 215 x 178
Weight kg
0.35 0.4 1.8 3.7
Terminal capacity
Cables
(box terminal)
Solid mm
2
1 x (0.75 - 4)
2 x (0.75 - 2.5)
1 x (0.75 - 16)
2 x (0.75 - 10)
1 x (25 - 70)
2 x (6 - 25)
1 x (4 - 185)
2 x (4 - 70)
Flexible with ferrule mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded mm
2
1 x 16
2 x 16
1 x (25 - 70)
2 x (6 - 25)
1 x (4 - 185)
2 x (4 - 70)
Solid or stranded AWG
1 x (18 - 10)
2 x (18 - 10)
1 x (14 - 8)
2 x (14 - 8)
1 x (12 - 2/0) 1 x (12 - 350 mcm
2 x (12 - 00)
Flat conductor
minimum mm 2 x 9 x 0.8 2 x 9 x 0.8
maximum mm
9 x 9 x 0.8 10 x 16 x 0.8
Tightening torque Nm
1.2 3.2 9 (> 10 mm²)
6 ( 10 mm²)
14 (> 10 mm²)
5 ( 10 mm²)
Control cables
Solid mm
2
1 x (0.75 - 4)
2 x (0.75 - 2.5)
1 x (0.75 - 4)
2 x (0.75 - 1.5)
1 x (0.75 - 4)
2 x (0.75 - 1.5)
1 x (0.75 - 4)
2 x (0.75 - 1.5)
Flexible with ferrule mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Stranded mm
2
Solid or stranded AWG 1 x (18 - 10)
2 x (18 - 10)
1 x (18 - 14)
2 x (18 - 16)
1 x (18 - 14)
2 x (18 - 16)
1 x (18 - 14)
2 x (18 - 16)
Tightening torque Nm
1.2 0.6 0.6 0.6
Screwdriver (flat blade) mm
0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5
Actuating circuit
Relay outputs
Number 1 (TOR) 2 (TOR,
RUN/READY)
1)
2 (TOR,
RUN/READY)
1)
2 (TOR,
RUN/READY)
1)
Max. voltage range V AC/DC = U
s
250 250 250
Max. load current A
1 1 1 1
1) Does not apply for soft starter DS7 with SmartWire-DT (DS7-…-D).

Table of Contents

Related product manuals