EasyManua.ls Logo

Eaton DS7 - Repair and Maintenance Switch

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Engineering
2.11 Motor connection
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 51
2.11.13 Repair and maintenance switch
Repair and maintenance switches disconnect all the poles (all the phases) in
the connection cable to a motor. This prevents voltage from being applied
and the motor from being started by accident during repair and maintenance
work.
The DS7 soft starter has a two-phase circuit with semiconductor elements in
the power section, one phase is always connected through directly.
Because of this, all the poles (all three phases) in two-phase controlled soft
starters should always be disconnected from mains voltage in the stop state
– with a contactor connected in series on the mains side, for example.
If a control system does not provide this potential isolation, it is advisable
to connect the motor through a repair or maintenance switch.
DANGER
In both the disabled and stop states of the soft starter when the
mains voltage is present (terminals 1L1, 3L2, 5L3), there is also
a dangerous voltage present at the output terminals (2T1, 4T2,
6T3) and therefore also on the motor cables and connection
terminals of the motor (U, V, W)!
Size 1 and 2
(4 - 32 A) Size 3 and 4 (41 – 200 A)
Figure 33: Dangerous voltage
M
3 ~
1L1 3L2 5L3
2T1
4T2
6T3
M
3 ~
1L1 3L2 5L3 PE
PE2T1
4T2
6T3

Table of Contents

Related product manuals