Basic module SIOX extension module
Field bus interface CAN bus, zero potential -
Data interfaces 1x data interface for SIOX Internal interface to basic module
2x serial RS232/RS485
1 x TTY (passive)
-
Archive memory Compressor run times, switching pulses,
quotas, messages
-
Real-time clock With power reserve, lithium cell
Type CRC 2450 N / 3 V Lithium
Battery life 10 years
Accuracy typically 12 minutes / year at 25 °C
-
Monitoring function Watchdog
Other interfaces Power supply for external SIOX
Temperature range Transport: -20 °C ... +80 °C
Operation: 0 °C ... +50 °C
Temperature change Transport: max. 20 K/h
Operation: max. 10 K/h
Relative humidity
(non-condensing)
Transport: 8% ... 80%
Operation: 20% ... 80%
Shock
according to DIN EN 60068-2-27
Transport and operation: 30 g
Vibration 10-150 Hz
according to DIN EN 60068-2-6
Transport and operation: 2 g
Atmospheric pressure Transport: 660 hPa ... 1060 hPa
Operation: 860 hPa ... 1060 hPa
Weight approx. 1600 g approx. 800 g
Protection rating IP20
CE conformity According to EC Directives
73/23/EEC Low Voltage Directive
89/336/EEC EMC Directive