EasyManua.ls Logo

ECKELMANN Compact GLT 3010 - Assignment of the Digital Inputs - 230 V AC; 24 V AC;DC

ECKELMANN Compact GLT 3010
119 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware: V2.18 / V--
26.10.2022
92/119
10.2.2 Assignment of the digital inputs - 230 V AC / 24 V AC/DC
Digital inputs on the base module
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
BEFORE connecting and disconnecting, it must be ensured that no voltage is present at all
connections of the controller.
Overvoltage category II / contamination degree 2: All connections of the device provided for
operation with 230 V AC supply voltage must be wired with the same outer conductor (L). 400 V AC
between neighbouring connection terminals is not permitted!
Mixed operation of the voltage levels! If digital inputs with low voltage (230 V AC) and safety extra-
low voltage (24 V AC/DC) are required on one SIOX module, these must be separated by a digital
input connected to PE!
Practical tip: Use of 2 separate SIOX modules to handle only one voltage level per module.
ATTENTION
Configuration of the digital inputs: For the digital inputs, ensure that the jumper position is correctly
configuredfor230VACor24VAC/DC.If230VACisappliedtoadigitalinputthathasbeen
configuredfor24VAC,thisresultsindestructionofthedigitalinputs!Fordetails,seechapter
Configuration of the digital inputs 230 V AC and 24 V AC/DC.
Damage to the connector socket: Observe the Handhabung breiter COMBICON-Stecker!

Table of Contents