10.2.1 Assignment of the 230 V AC power supply
Connection:Onlyonbasemodule–terminalblock,upperrightattheback
SUPPLY
Description Terminal No. Connection Function
230 V AC N
L
PE
Neutral conductor
Phase 230 V AC
Earth conductor
Power supply
Connection to the power supply
Requirements for the connection cable
As the controller does not have an integrated disconnecting device in the form of a power switch, the following
mustbeimplemented:
a) a switch or circuit breaker must be installed in the system or building installation,
b) this must be suitably positioned and easily accessible for the user and
c) this must be labelled as disconnecting device for the device.
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock! BEFORE
connecting and disconnecting, it must be checked that the 230 V AC power supply cable is
disconnected from the power supply! The controller is only permitted to be connected to the
intended mains power supply!
•
•
In order to fuse the mains power line, a circuit breaker with the following characteristics must be used:
Rated current for 230 V AC: 6 A
Tripping characteristic (type): B
Afterconnectionofthe230VACpowersupply,thegreenPOWERLEDflashes,fordetailsseechapter
Status LEDs