EasyManua.ls Logo

ECKELMANN Compact GLT 3010 - Page 25

ECKELMANN Compact GLT 3010
119 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware: V2.18 / V--
26.10.2022
25/119
The analogue inputs (0..10 V / 4..20 mA) are configured in the "Module parameters" tab (see Controller
configuration). The selection can be found as follows:
GLT3010_V2 → Analog IO → 7 Analog Inputs
Select "Module parameters" on the right-hand side:
For orientation, a Default column is provided in which the factory setting is described. The Value column shows
the setting currently in use. The desired behaviour of the interfaces for 0..10 V or 4..20 mA is set via the drop-
down selection boxes:
The following screenshot in the controller configuration under Controller GLT 3010_V2, in the Analogue IO
section, shows that the base module (called STANDARD) has 7 analogue inputs. Clicking on [+] opens the
following display:
Explanation: The seven analogue inputs have the IEC addresses %IW42 .. %IW48
ThepresetvariablenamesAIN1..AIN7canbeuseddirectlyinCODESYS,e.g.forIF AIN7 > 16000 then
When changing the configuration of the analogue inputs, the jumpers located on the main board must
be reconfigured.
Practical tip: For better readability of the CODESYS program, meaningful process variable names
should be defined via theSignal List and then used.

Table of Contents