CAUTION:
Do not keep the c
ooling water supply on if the pump is not going to be required for
some me, otherwise, water condensing outside the pipe might cause corrosion of
element.
Refer to Table: Stop sequences for the stop sequences.
Table 16
Stop sequences
Sequence Descripon
Stop sequence
Inlet purge gas valve is opened.
Inlet isolaon valve is closed (if ed).
Pump runs for 15 minutes before stopping.
Close all gas purge aer the pump stops.
Switch o water-cooling by closing both inlet and outlet aer
at least 60 minutes aer pump stops
If the pump is not going to be required for some me, switch o the electrical supply
and the cooling water supply. Seal the pump inlet and exhaust to prevent any moisture
in the atmosphere from corroding the pumping mechanism.
6.3 Automac shut down
Normally, if an alarm condion exists, the control system will shut down the dry
pumping system. When the dry pumping system shuts down, the pump stops.
Table 17
Alarm acons
Alarm descripon
Alarm stops the dry pump
EMS Yes
Stator temperature is over 130° C Yes
Motor snap switch tripped Yes
Overload relay tripped Yes
Inverter overload Yes
6.4 Unplanned shut down and alarms
The dry pumping s
ystem is ed with thermal protecon sensors that will give warnings
and alarms. Refer to Table: Pump protecon sensors.
Table 18
Pump protecon sensors
Sensor
Warning condion triggered Alarm condion triggered
DP TEMP temperature
EXS750 120 °C 130 °C
EXS450 120 °C 130 °C
Refer to Automac shut down on page 52 for informaon about alarms and automac
shutdown condions.
07/2021 - ©Edwards Limited
Page 52A41870880_A
A41870880_A - Operaon