37
Parallel Tab
(Page 2 / 2)
Eeps_day: Daily load (L1-L2) power output
Eeps_all: Total load (L1-L2) power output
EepsL1N_day: Load (L1-N) output power in a day
EepsL1N_all: Total power output of load (L1-N)
EepsL2N_day: Load (L2-N) output power in a day
EepsL2N_all: The total power output of load (L1-N)
________________________________________________________________
Parallel Role: Role of the inverter in the parallel state
(master and slave)
Parallel Type: Type of parallel connection, single phase or
three phase
Parallel Phase: Parallel phase (U, V, or W) for three phase
configurations
Parallel Num: Number of parallel inverters
Parallel Addr: Inverter parallel address
________________________________________________________________
Status: Current status of the inverter
NextStatus: Next status of the inverter
FaultCode: Inverter error code
AlarmCode: Inverter alarm code
Vbus1: Voltage of BUS1
Vbus2: Voltage of BUS2
VbusP: Positive BUS voltage
VbusN: Negative voltage of the BUS
T1: Temperature of the I/O board (the highest value).
Normal <87°C; Warning >87°C; Fault ≥95°C
T2: Temperature of the motherboard (take the highest value). Normal <90°C; Warning >90°C;
Fault ≥105°C
ExitReason1: Used by engineering for debugging. This should be blank unless there is an issue.
ExitReason2: Used by engineering for debugging. This should be blank unless there is an issue.
Run_Trace: Used by engineering for debugging. This should be blank unless there is an issue.