Server enabled specify if BACnet server is enabled or not
Device ID device ID in BACnet network
Password device password
Object priority object priority
Add group address to object name add automatically the address to object name
Port port number
BBMD IP BACnet router IP. When router IP and port are set, LM will act as a foreign
device and will attempt to register with BACnet router.
BBMD port BACnet router port. When router IP and port are set, LM will act as a foreign
device and will attempt to register with BACnett router
BBMD lease time (seconds) registration resend interval
To make KNX/EIB objects BACnet readable/writable, mark necessary objects in LogicMachine as
r as Binary Values, other numeric values will appear as
Analog Values. Other types are not currently supported. KNX bus write changes priority array
value at configured object priority index

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Embedded Systems LogiMachine5 Power and is the answer not in the manual?

Embedded Systems LogiMachine5 Power Specifications

General IconGeneral
ProcessorARM Cortex-A9
Operating SystemLinux
Memory1GB DDR3
Storage8GB eMMC
Digital I/O16x GPIO
Operating Temperature-20°C to 60°C