177
Value_delta New value is sent when the difference between previously sent value and
current value is larger than delta. Defaults to 0 (send after each read) (Number)
Value_multiplier Multiply resulting value by the specified number, value = value_base
+ value * value_multiplier (Number)
Value_bitmask Bit mask to apply, shifting is done automatically based on least
significant 1 found in the mask (Number)
Value_nan Array of 16-bit integers. If specified and read operation returns the same
array no further processing of value is done (Array)
Value_conv Apply one of built-in conversion functions (String, Internal)
Value_custom Name of a built-in enumeration or a list of key -> value mapping,
resulting value will be 0 if key is not found (String/Object)
Internal Not visible to user when set to true, should be used for scale registers
(Boolean)
Units KNX object units/suffix (String)
Address_scale Address of register containing value scale, value = value * 10 ^ scale
(Number)
Read_count Number of register to read at once (for devices that only support reading
of a specific block of registers) (Number)
Read_swap Swap register order during conversion (endianness) (Boolean)
Read_offset Position of first register of data from the block of registers (0-based)
(Number)
When the Modbus device profile file is created, upload it by clicking on Profiles button.