G3 Series EtherCAT
TM
Technical Manual
5-44
Subject to change without notice
www.asco.com/g3
Advanced Settings – Parameters Lock
1. Press the SET button to enter the Parameters sub-menu.
2. Press the NEXT button to scroll through the choices to
enable or disable the feature.
g. UNLOCKED (Factory Default)
h. LOCKED
i. RETURN (this will return you to the main menu)
Press the SET button to confirm your choice.
By choosing LOCKED, all settable parameters will be read
only via the graphic display. UNLOCKED, the factory
default, will allow all parameters to be settable through the
graphic display.
Please note that all parameters are read only, regardless of
this setting, when an IO connection between the
communication module and the controller (PLC) is present
3. Press the NEXT button to select Yes or No to accept the
selection.
e. Selecting No will bring you back to the main
menu.
f. Selecting Yes will take you to the following apply
changes menu.
Press the SET button to confirm your choice.
Apply Changes Steps
4. Press the NEXT button to select either NOW or LATER.
e. Selecting NOW will cause the node to reset and
apply the new setting.
f. Selecting LATER will cause the new setting to be
saved in memory, you must accept the saved
changes before your next power cycle otherwise
they will be lost.
Press the SET button to confirm your choice.
UNLOCKED
UNLOCKED
LOCKED
RETURN
LOCKED Y N
LOCKED Y N