Description of parameters (FF configuration program) Cerabar S/Deltabar S
58 Endress+Hauser
6.3.4 Totalizer Transducer Block (only Deltabar S)
DAT_HANDLING/
HistoROM CONTROL
Selection
Index: 47
Data type: Unsigned8
Access: Auto, OOS
For selecting the direction for copying the data.
See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S), Section 5.4
"HistoROM
®
/M-DAT (optional)".
Prerequisite:
•A HistoROM
®
/M-DAT is attached to the electronic insert
(HISTO_ROM_AVAILABLE/HistoROM AVAIL. = yes)
Options:
Abort
•HistoROM Device
Device HistoROM
Factory setting:
Abort (if HistoROM
®
/M-DAT is connected to the electronic insert)
PRESSURE_1_UNIT/
PRESS. ENG. UNIT
Display
Index: 48
Data type: Unsigned16
Access: Read only
Displays the pressure unit selected.
The pressure unit is selected by means of the CAL_UNIT parameter ( Page 34) in the
Pressure Transducer Block.
TEMPERATURE_UNIT/
TEMP. ENG. UNIT
Display
Index: 49
Data type: Unsigned16
Access: Read only
Displays the temperature unit selected.
The temperature unit is selected by means of the SECONDARY_VALUE_UNIT parameter
( Page 35) in the Pressure Transducer Block.
Totalizer Transducer Block
Parameter Description
TOTALIZER_1_VALUE/
TOTALIZER 1
Display
Index: 12
Data type: DS-65
Access: Read only
The TOTALIZER_1_VALUE parameter is a structured parameter consisting of two elements.
VALUE
Displays the total flow value of totalizer 1. You can reset the value with the
TOTALIZER_1_RESET/RESET TOTALIZER1 parameter.
STATUS
Displays the status.
!
Note!
You can transfer the value and status of the TOTALIZER_1_VALUE parameter via the
CHANNEL parameter ( Page 67) in the Analog Input Block. For this purpose, the
CHANNEL must be set to "6".
You can transfer the value and status of the PTOTALIZER_1_VALUE parameter via the
CHANNEL parameter in the Discrete Output Block. For this purpose, the CHANNEL must
be set to "2".
TOTALIZER_1_UNIT/
TOTAL. 1 ENG. UNIT
Selection
Index: 13
Data type: Unsigned16
Access: Auto, OOS
Select unit for totalizer 1.
Depending on the setting in the FLOW_TYPE/FLOW-MEAS. TYPE parameter (Page 46),
this parameter offers a list of volume, norm volume, standard volume and mass units. When a
new volume or mass unit is selected, totalizer-specific parameters are converted and
displayed with the new unit within a unit group. When the flow mode is changed, the
totalizer value is not converted.
Factory setting:
m
3
FLOW_TYPE/
FLOW-MEAS. TYPE
Display
Index: 14
Data type: Unsigned8
Access: Read only
Displays the flow type selected.
The flow type is selected by means of the FLOW_TYPE/FLOW-MEAS. TYPE parameter
( Page 46) in the Pressure Transducer Block.
Service Transducer Block
Parameter Description