Commissioning Proline Promag 55 PROFIBUS DP/PA
100 Endress+Hauser
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 2 to 4) consists of the functions SETTOT and
TOTAL.
With this module combination:
The totalizer can be controlled via the automation system (SETTOT).
The totalizer value is transmitted, including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
0 = Totalize (factory setting)
1 = Reset totalizer (the totalizer value is reset to 0)
2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing continues
automatically. The control variable does not have to be changed to 0 again to restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the MODETOT
function ä 101.
TOTAL function
For a description of the TOTAL function, refer to TOTAL module ä 99.
Data structure of the SETTOT_TOTAL module combination
Output data Input data
SETTOT TOTAL
Byte 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Totalizer value (IEEE 754 floating point number) Status