Commissioning Proline Promag 55 PROFIBUS DP/PA
100 Endress+Hauser
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 2 to 4) consists of the functions SETTOT and
TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer value is transmitted, including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
• 0 = Totalize (factory setting)
• 1 = Reset totalizer (the totalizer value is reset to 0)
• 2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing continues
automatically. The control variable does not have to be changed to 0 again to restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the MODETOT
function ä 101.
TOTAL function
For a description of the TOTAL function, refer to TOTAL module ä 99.
Data structure of the SETTOT_TOTAL module combination
Output data Input data
SETTOT TOTAL
Byte 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Totalizer value (IEEE 754 floating point number) Status