EasyManua.ls Logo

Endress+Hauser Proline Promag 55 - PROFIBUS PA connection diagram

Endress+Hauser Proline Promag 55
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Proline Promag 55 PROFIBUS DP/PA Wiring
Endress+Hauser 49
4.3.4 PROFIBUS PA connection diagram
Permanent assignment board (order version 55***-***********H)
A0002593
Fig. 33: Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(14 AWG)
A View A (field housing)
B View B (stainless steel field housing)
C View C (wall-mount housing)
a Connection compartment cover
b Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
c Ground terminal for protective ground
d Fieldbus cable:
Terminal No. 26: PA + (with reverse polarity protection)
Terminal No. 27: PA – (with reverse polarity protection)
e Fieldbus cable shield ground terminal
Observe the following:
the shielding and grounding of the fieldbus cable ä 39
that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)
d
c
e
b
27
25
23
21
2
1
26
24
22
20
L1 (L+)
PA +
N (L-)
PA
f
PA
PA +
1
2
ce
f
b
d
222320 21 24
25
26
27
L1 (L+)
N (L–)
C
a
d
b
a
A
B
d
b
d
b

Table of Contents

Other manuals for Endress+Hauser Proline Promag 55

Related product manuals