Proline Promag 55 PROFIBUS DP/PA Wiring
Endress+Hauser 49
4.3.4 PROFIBUS PA connection diagram
Permanent assignment board (order version 55***-***********H)
A0002593
Fig. 33: Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(14 AWG)
A View A (field housing)
B View B (stainless steel field housing)
C View C (wall-mount housing)
a Connection compartment cover
b Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
– Terminal No. 1: L1 for AC, L+ for DC
– Terminal No. 2: N for AC, L- for DC
c Ground terminal for protective ground
d Fieldbus cable:
– Terminal No. 26: PA + (with reverse polarity protection)
– Terminal No. 27: PA – (with reverse polarity protection)
e Fieldbus cable shield ground terminal
Observe the following:
– the shielding and grounding of the fieldbus cable ä 39
– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)