Installation Proline Promag 55 PROFIBUS DP/PA
12 Endress+Hauser
Transporting flanged devices DN > 300 (12")
Use only the metal eyes on the flanges for transporting the device, lifting it and positioning the
sensor in the piping.
"
Caution!
Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing. This
would buckle the casing and damage the internal magnetic coils.
A0004295
Fig. 5: Transporting sensors with DN > 300 (12")
3.1.3 Storage
Note the following points:
Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors ä 145.
The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
Choose a storage location where moisture does not collect in the measuring device. This will help
prevent fungus and bacteria infestation which can damage the liner.
Do not remove the protective plates or caps on the process connections until the device is ready
to install. This is particularly important in the case of sensors with PTFE linings.