Technical data Proline Promag 55 PROFIBUS DP/PA
142 Endress+Hauser
10.1.4 Output
Output signal Current output
Active/passive selectable, galvanically isolated, time constant selectable (0.01 to 100 s),
Full scale value adjustable, temperature coefficient: typically 0.005% o.r./°C, resolution: 0.5 μA
Active: 0/4 to 20 mA, R
L
max. 700
Passive: 4 to 20 mA; supply voltage V
S
18 to 30 V DC; R
i
150
Pulse/frequency output:
Active/passive selectable, galvanically isolated
Active: 24 V DC, 25 mA (max. 250 mA during 20 ms), R
L
> 100
Passive: open collector, 30 V DC, 250 mA
Frequency output: full scale frequency 2 to 10000 Hz (f
max
= 12500 Hz), on/off ratio 1:1,
pulse width max. 2 s
Pulse output: pulse value and pulse polarity selectable, pulse width configur. (0.05 to 2000 ms)
PROFIBUS DP interface
Transmission technology (Physical Layer): RS485 according to ANSI/TIA/EIA-485-A: 1998,
galvanically isolated
Profile Version 3.0
Data transmission rate: 9.6 kBaud to 12 MBaud
Automatic identification of data transmission rate
Function blocks: 2 × analog input, 3 × totalizer
Output data: volume flow, calculated mass flow, totalizer 1 to 3
Input data: positive zero return (ON/OFF), totalizer control, value for local display
Cyclic data transmission compatible with previous model Promag 35S
Bus address adjustable via miniature switches or local display (optional) at the measuring device
PROFIBUS PA interface
Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
Profile version 3.0
Current consumption: 11 mA
Permissible supply voltage: 9 to 32 V
Bus connection with integrated reverse polarity protection
Error current FDE (Fault Disconnection Electronic): 0 mA
Function blocks: 2 × analog input, 3 × totalizer
Output data: volume flow, calculated mass flow, totalizer 1 to 3
Input data: positive zero return (ON/OFF), totalizer control, value for local display
Cyclic data transmission compatible with previous model Promag 35S
Bus address adjustable via miniature switches or local display (optional) at the measuring device
Signal on alarm Current output:
Failsafe mode selectable (e.g. in accordance with NAMUR recommendation NE 43)
Pulse/frequency output:
Failsafe mode selectable
Relay output:
De-energized by fault or power supply failure
PROFIBUS DP/PA
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0
Load See "Output signal"