Proline Promag 55 PROFIBUS DP/PA Installation
Endress+Hauser 21
3.2.9 Length of connecting cable
In order to ensure measuring accuracy, comply with the following instructions when installing the
remote version:
• Secure the cable run or route the cable in a conduit. Movement of the cable can falsify the
measuring signal, particularly if the fluid conductivity is low.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter, if necessary.
• The permissible cable length L
max
depends on the fluid conductivity ( å 16, å 17).
• The maximum connecting cable length is 10 m (32.8 ft) when empty pipe detection
(EPD ä 117) is switched on.
Promag S
A0006116
Fig. 16: Permitted lengths for connecting cable in remote version, as a function of the conductivity of the fluid
Gray shaded area = permissible area
L
max
= Length of connecting cable
Promag H
A0010734
Fig. 17: Permitted lengths for connecting cable in remote version, as a function of the conductivity of the fluid
Gray shaded area = permissible area
L
max
= Length of connecting cable
[µS/cm]
50
40
30
20
10
5
0
10020304050
[m]
L
max
L
max
50 100 1500
[ft]
200
100
5
10 100 200
L
max
[m][m]
[µS/cm]
L
max
[ft]
200 6000
400