Proline Promag 55 PROFIBUS DP/PA Wiring
Endress+Hauser 45
4.3 Connecting the measuring unit
4.3.1 Terminal assignment
!
Note!
The electrical characteristic quantities are listed in the "Technical data" section.
PROFIBUS DP
"
Caution!
Only certain combinations of submodules (see Table) on the I/O board are permissible. The
individual slots are also marked and assigned to the following terminals in the connection
compartment of the transmitter:
• "INPUT / OUTPUT 3" slot = terminals 22/23
• "INPUT / OUTPUT 4" slot = terminals 20/21
PROFIBUS PA
Terminal No. (inputs / outputs)
Order version 20 (+) / 21 (–)
Submodule on
slot No. 4
22 (+) / 23 (–)
Submodule on
slot No. 3
24 (+) / 25 (–)
Fixed on
I/O board
26 = B (RxD/TxD-P)
27 = A (RxD/TxD-N)
Fixed on I/O board
55***-***********J – – +5V (ext. termination) PROFIBUS DP
55***-***********V Relay output 2 Relay output 1 Status input PROFIBUS DP
55***-***********P Current output Frequency output Status input PROFIBUS DP
Terminal No. (inputs / outputs)
Order version 20 (+) / 21 (–) 22 (+) / 23 (–) 24 (+) / 25 (–) 26 = PA +
27 = PA –
55***-***********H – – – PROFIBUS PA
With integrated reverse polarity protection