Operation Proline Promag 55 PROFIBUS DP/PA
56 Endress+Hauser
5Operation
5.1 Quick operation guide
The user has a number of options for configuring and commissioning the device:
1. Local display (option) ä 57
The local display enables you to read all important variables directly at the measuring point,
configure device-specific parameters in the field and perform commissioning.
2. Operating programs ä 63
The configuration of profile and device-specific parameters is primarily done via the PROFIBUS
interface. You can obtain special configuration and operating programs from various
manufacturers for these purposes.
3. Jumpers/miniature switches for hardware settings
–PROFIBUS DP ä 66
–PROFIBUS PA ä 71
You can make the following hardware settings using a jumper or miniature switches on the
I/O board:
• Address mode configuration (select software or hardware addressing)
• Device bus address configuration (for hardware addressing)
• Hardware write protection enabling/disabling
!
Note!
A description of the configuration of the current output (active/passive) and the relay output
(NC contact/NO contact) is contained in the "Hardware settings" section ä 69.
A0001318
Fig. 41: Methods of operating PROFIBUS PA/DP
1 Local display for device operation in the field (option)
2A Configuration/operating programs (e.g. FieldCare) for operation via PROFIBUS DP/PA
2B Configuration/operating program for operating by means of the FXA193 service interface (e.g. FieldCare)
3 Jumper/miniature switches for hardware settings (write protection, device address, address mode)
2A
3
1
Esc
E
-
+
Esc
E
+
-
XXX.XXX.XX
Esc
E
-
+
FXA193
2B