Proline Promag 55 PROFIBUS DP/PA Wiring
Endress+Hauser 55
4.6 Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications Notes
Are cables or the device damaged (visual inspection)? –
Electrical connection Notes
Do the cables comply with the specifications? PROFIBUS DP ä 36
PROFIBUS PA ä 37
Sensor cable ä 44
Do the cables have adequate strain relief? –
Is the cable type route completely isolated?
Without loops and crossovers?
–
Are the power supply and fieldbus cables correctly connected? See the wiring diagram inside
the cover of the connection
compartment
Are all screw terminals firmly tightened? –
Have the measures for grounding/potential equalization been correctly
implemented?
ä 52
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?
ä 54
Are all housing covers installed and firmly tightened? –
Electrical connection of PROFIBUS PA Notes
Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
connected with each other correctly?
–
Has each fieldbus segment been terminated at both ends with a bus terminator? PROFIBUS DP ä 68
Has the max. length of the fieldbus cable been observed in accordance with the
PROFIBUS specifications?
PROFIBUS DP ä 36
PROFIBUS PA ä 37
Has the max. length of the spurs been observed in accordance with the PROFIBUS
specifications?
PROFIBUS DP ä 36
PROFIBUS PA ä 37
Is the fieldbus cable fully shielded and correctly grounded? ä 39