Note!
The control (e.g. switching on positive zero return) is executed by cyclic data transmission if the
output byte switches from "0" to the bit pattern in question. The output byte must always switch
from "0". A switchback to "0" does not have any effect.
Example (change the output byte)
Output data
EMPTY_MODULE module
The measuring device is a so-called modular PROFIBUS slave. In contrast to a compact slave, the
structure of a modular slave is variable - it consists of several individual modules. In the GSD file,
the individual modules are described with their individual properties. The modules are permanently
assigned to the slots, i.e. the sequence or arrangement of the modules must be observed when
configuring the modules. Gaps between configured modules have to be assigned the
EMPTY_MODULE module.
For a more detailed description ä 96.
Module Control variables
CONTROL_BLOCK
0 2: Positive zero return ON
0 3: Positive zero return OFF
0 8: UNIDIRECTIONAL measuring mode
0 9: BIDIRECTIONAL measuring mode
0 24: Run UNIT TO BUS function
Control variables that are executed only if the measuring device is equipped
with the optional Electrode Cleaning Circuit (ECC)
0 5: ECC OFF
0 6: ECC ON
Control variables that are executed only if additional "Advanced diagnostics"
software is installed in the measuring device.
0 25: Warning mode "Advanced Diagnostics" OFF
0 26: Warning mode "Advanced Diagnosis" ON
0 60: DISPLAY_VALUE assignment density ON
0 61: DISPLAY_VALUE assignment density OFF
0 70: Start determining the user reference status
0 74: Acquisition mode OFF
0 75: Acquisition mode, PERIODICAL
0 76: Acquisition mode, MANUAL (SINGLE SHOT)
0 78: Start manual determination of the advanced diagnostics parameters
From To Result
0 2 Positive zero return is switched on.
2 0No effect
0 3 Positive zero return is switched off.
3 2No effect
Byte 1
Control