Proline Promag 55 PROFIBUS DP/PA Technical data
Endress+Hauser 147
Promag H
Sensor:
• DN 2 to 25: –20 to +150 °C (–4 to +302 °F)
• DN 40 to 100: –20 to +150 °C (–4 to +302 °F)
Seals:
• EPDM: –20 to +150 °C (–4 to +302 °F)
• Silicone: –20 to +150 °C (–4 to +302 °F)
• Viton: –20 to +150 °C (–4 to +302 °F)
• Kalrez: –20 to +150 °C (–4 to +302 °F)
Conductivity Minimum conductivity:
• 5 μS/cm for all liquids (incl. demineralized water)
!
Note!
In the remote version, the required minimum conductivity is also influenced by the length of the
cable ä 21
Fluid pressure range (nominal
pressure)
Promag S:
• EN 1092-1 (DIN 2501): PN 10 (DN 200 to 600 / 8 to 24"), PN 16 (DN 65 to 600 / 2½ to 24"),
PN 25 (DN 200 to 600 / 8 to 24"), PN 40 (DN 15 to 150 / ½ to 6")
• ANSI B16.5: Class 150 (DN ½ to 24"), Class 300 (DN ½ to 6")
• JIS B2220: 10 K (DN 50 to 300 / 2 to 12"), 20 K (DN 15 to 300 / ½ to 12")
• AS 2129: Table E (DN 25/1", DN 50/2")
• AS 4087: Cl. 14 (DN 50/2")
Promag H:
The permissible nominal pressure depends on the process connection and seal:
• 40 bar: flange, weld nipple (with O-ring seal)
• 16 bar: all other process connections