Proline Promag 55 PROFIBUS DP/PA Commissioning
Endress+Hauser 93
PROFIBUS Profile GSD file:
The function of the profile GSD file is defined by the PROFIBUS Profile Specification 3.0. The
function is restricted compared to the manufacturer-specific GSD file (complete device
functionality). However, similar devices from different manufacturers can be interchanged with the
profile GSD file without the need to reconfigure (interchangeability).
Profile GSD (multi-variable) with the ID number 9760Hex: this GSD contains all function blocks
such as AI, DO, DI etc. This GSD is not supported by Promag.
!
Note!
• Before configuration takes place, a decision should be made as to which GSD is to be used to
operate the system.
• It is possible to change the setting via the onsite display or via a Class 2 master. For adjustment
via the onsite display, refer to ä 86.
Supported GSD files: ä 64
Each device receives an identification number (IDNo.) from the Profibus User Organization (PNO).
The name of the Device Master File (GSD file) is derived from this.
For Endress+Hauser, this ID No. starts with the manufacturer ID 15xx.
In order to ensure clarity and make assignment easier, the GSD names (with the exception of type
files) at Endress+Hauser are as follows:
Name of the PROFIBUS Profile GSD file
Source
Internet (GSD library of the PROFIBUS User Organization) www.PROFIBUS.com
Promag 35 GSD file:
Promag 35 with Profile Version 2.0 is the precursor to the Promag 55. If Promag 35 is already being
operated in the system and the measuring device has to be replaced, Promag 55 can be used as a
replacement device without having to reconfigure the PROFIBUS DP network.
Further information ä 95.
EH3_15xx EH = Endress+Hauser
3 = Profile 3.0
_ = Standard ID
15xx = ID No.
EH3x15xx EH = Endress+Hauser
3 = Profile 3.0
x = Extended ID
15xx = ID No.
ID No. Profile GSD file
PROFIBUS DP 9742 (Hex) PA039742.gsd
PROFIBUS PA 9742 (Hex) PA139742.gsd