Commissioning Proline Promass F 300 EtherNet/IP
108
Navigation
"Setup" menu → Current input
‣
Current input 1 to n
Terminal number
→ 108
Signal mode
→ 108
0/4 mA value
→ 108
20 mA value
→ 108
Current span
→ 108
Failure mode
→ 108
Failure value
→ 108
Parameter overview with brief description
Parameter Prerequisite Description User interface /
Selection / User
entry
Factory setting
Terminal number – Shows the terminal numbers
used by the current input
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Signal mode The measuring device is not
approved for use in the
hazardous area with type of
protection Ex-i.
Select the signal mode for the
current input.
• Passive
• Active
Active
0/4 mA value – Enter 4 mA value. Signed floating-point
number
0
20 mA value – Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• 0...20 mA
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
Failure mode – Define input behavior in alarm
condition.
• Alarm
• Last valid value
• Defined value
Alarm
Failure value In the Failure mode
parameter, the Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
Signed floating-point
number
0