6 Commissioning PROline Prosonic Flow 93 PROFIBUS-DP/-PA
108 Endress+Hauser
Configuration data
Byte length
(Input)
Byte length
(Output)
Data blocks Status Access type GSD
Block designation
GSD
Extended block
identification
GSD
Standard block
identification
0...4 Volume flow CH1 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 Sound velocity CH1 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
10...14 Flow velocity CH1 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
15...19 Volume flow CH2 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
20...24 Sound velocity CH2 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
25...29 Flow velocity CH2 +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
30...34 Volume flow average +
status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
35...39 Sound velocity average
+ status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
40...44 0 + 1 Totalizer 1 +
status + control
active read +
write
SETTOT_MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
45...49 2 + 3 Totalizer 2 +
status + control
active read +
write
SETTOT_MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
50...54 4 + 5 Totalizer 3 +
status + control
active read +
write
SETTOT_MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
6...10 Display value active write DISPLAY_VALUE 0x82, 0x84,
0x08, 0x05
0xA4
11 Control variable active write CONTROL_BLOCK 0x20 0x20